Sizing

 

Use the wizard to determine the required size,
or if you prefer you can refer to the table below.

Flue Sizing Wizard

 

100
mm

130
mm

150
mm

180
mm

200
mm

230
mm

250 to
400mm

Gas Boiler - Forced Draught

 

Input up to 25kW

Input 25kW-45kW

 

Input 45kW-50kW

Input 50kW-75kW

 

Input 75kW-100kW

Input over 100kW

 

•2

Gas Fires

'Inset' to BS7977-1 2002

•1

'Decorative' to BSEN 509:2000

Gas Oil (35 sec Class D) Heating Boiler

Output up to 25kW

Input 25kW to 45kW

Input 45kW to 70kW

Input 70kW to 100kW

Output over 100kW

•3

•3

•3

Solid Fuel Heating Boiler

Output up to 20kW

•S

•SC

Output 20kW to 30kW

•S

•SC

•SC

Output 30kW to 60kW

•SC

•SC

•C

Open Fires (Standard opening) 500mm x 550mm

•200
mm

'Avant Garde' Feature Open Fires

•4

Room Heaters

•S

Wood burning Stoves/Cookers. Use only seasoned wood which has been stored 1/2 years in dry conditions.

•180
mm

Inglenook or nonstandard opening. The Cross sectional area of the chimney liner must be a minimum of 15% of the total cross sectional area of the fireplace opening.

•230
mm

 

KEY TO ANNOTATION IN TABLES

1 Subject to appliance manufacturer's testing criteria.

2. Subject to manufacturer's input rating and chimney height.

3. Subject to manufacturer's output rating and chimney height.

4. Min 300mm depending on opening, chimney size and height.

S Smokeless fuel only.

SC Smokeless fuel or coal.This information and sizes are provided as a nominal guide only. Flue sizing for appliances, particularly commercial/industrial applications will vary depending on siting details and appliance manufacturer's instructions and design criteria. These will override the sizing guide below and reference must be made to appliance manufacturer.

Print pageContactSitemap